Thread: San Marino 2 Group boiler not filling when connected to generator

  1. #1
    Junior Member
    Join Date
    May 2011
    Posts
    8

    Unhappy San Marino 2 Group boiler not filling when connected to generator

    Gene Cafe Coffee Roaster $850 - Free Beans Free Freight
    I've just bought a Dunlite 7KVA inverter generator to run my old reliable 2 group San Marino. I gave it a test run before taking the setup into the field and the boiler would not fill. Everything else was working - pump, heating element, grinder etc. When I disconnected the genny and plugged into mains power the boiler called for water straight away? The genny specs are - 240 volts, current - 27.1A, frequency - 50Hz, max power 7.0KVA, rated power - 6.5KVA.

    Anyone have any ideas?

    Thanks

    Rowan

  2. #2
    Senior Member sprezzatura's Avatar
    Join Date
    Dec 2013
    Location
    Hervey Bay, QLD
    Posts
    930
    Quote Originally Posted by thegordon View Post
    I've just bought a Dunlite 7KVA inverter generator to run my old reliable 2 group San Marino. I gave it a test run before taking the setup into the field and the boiler would not fill. Everything else was working - pump, heating element, grinder etc. When I disconnected the genny and plugged into mains power the boiler called for water straight away? The genny specs are - 240 volts, current - 27.1A, frequency - 50Hz, max power 7.0KVA, rated power - 6.5KVA.

    Anyone have any ideas?

    Thanks

    Rowan
    It's possible the boiler fill solenoid coil is failing. Why it won't do this on mains is odd unless there's an issue we don't know about. If the fill probe isn't signalling no earth when the boiler water level drops below the probe tip there's a problem with the auto-fill circuit when on generator.
    thegordon likes this.

  3. #3
    Mal Dimal's Avatar
    Join Date
    Oct 2004
    Location
    Warwick, QLD
    Posts
    16,772
    G'day Rowan...

    It might be worth your while to request that the output of the generator be checked on a Scope (Oscilloscope) to ensure that there is nothing untoward going on, with the output waveform. The manufacturer's blurb states that the output is "Pure Sine Wave" but it wouldn't hurt to verify that. Where electronic hardware is concerned, any "noise" in the waveform can cause unexpected results...

    Mal.
    thegordon and sprezzatura like this.

  4. #4
    Senior Member sprezzatura's Avatar
    Join Date
    Dec 2013
    Location
    Hervey Bay, QLD
    Posts
    930
    It certainly sounds like a waveform problem with the auto fill circuit issue. It's low voltage. I wonder if the noise might affect the low voltage to the flow meters? Erratic volumes?
    thegordon likes this.

  5. #5
    Mal Dimal's Avatar
    Join Date
    Oct 2004
    Location
    Warwick, QLD
    Posts
    16,772
    Yes mate, anything's possible until that potential issue is put to bed...

    Mal.
    thegordon likes this.

  6. #6
    Junior Member
    Join Date
    May 2011
    Posts
    8
    Thanks for your replies Mal & Sprezzatura.

    I've been on the phone to the electrician at Dunlite who thinks the issue may be the way the genny is earthed is different to how mains power is earthed? He thinks by making a connection at the back of the power point on the genny between the earth and neutral pins that it should solve the problem. I'm heading up to Dunlite with the San Marino and genny tomorrow.

    Cheers

    Rowan
    Dimal and sprezzatura like this.

  7. #7
    Senior Member sprezzatura's Avatar
    Join Date
    Dec 2013
    Location
    Hervey Bay, QLD
    Posts
    930
    It sounded like an earth issue as that's how the auto-fill circuit works to fill the boiler. Please let us know how you go so we can add this knowledge to our t/s skills in the future.

  8. #8
    Junior Member
    Join Date
    May 2011
    Posts
    8
    Behmor Brazen - $249 - Free Freight
    Easy fix. Their sparky pulled out the two PPs connected a wire between earth and neutral on each one, put it all back together and bingo the boiler fills.

    Cheers

    Rowan